Wuhan Feite Electric Co., Ltd.

ZN63A(VS1)-12 indoor high voltage vacuum circuit breaker

ZN63A(VS1)-12 indoor high voltage vacuum circuit breaker
Product Detailed

1.vacuum circuit breaker
2.Reliable and maintenance free
3.Long service life,non exploration
4.Short delivery time

ZN63A(VS1)-12 vacuum circuit breaker is a type of indoor power distribution equipment. It ‘s developed by bring in technical of ABB cooperation combining our domestic situation. It can be used in double deck cabinet, fixed cabinet for protecting and controlling in transformer substation and power system of industrial and mining enterprises. They are especially appropriate to oil forbidden, maintenance free, and frequent operation places, strictly stick to the stander of GB-1984,DL403and IEC No.56,No.694.

Main characters:

Operation mechanism and circuit breaker are combined together, making the layout reasonable, concision and beauty.  Stereoscopic isolate cylinder can protect circuit breaker from influence outside. Thus it can be applied to every special condition.Handcart and fixed type meet the need of different mounting requirement.Maintenance free. Only a little cleaning or lubrication would be enough.

 Ambient condition

1 Ambient temperature: max +40°C min -15°C(conveyance under -30°C is allowed)

2 Altitude: ≤1000m

3 Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity≤90%; daily average saturated vapor pressure ≤2.2*10-3 MPa; monthly average value   ≤1.8*10-3 MPa

4 Earthquake intensity: ≤8 degree

5 The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution

 

Order instruction

Complete model and order quantity of the product

Rated current, rated voltage

Rated short circuit breaking current, operation voltage

Required accessory and quantity

Other requirement please contact with us directly 

 

Main Technical Data    
Rated voltage                                                             kv12
Rated lighting impulse withstand voltagekvInterphase or to ground 75,fructure 80
Rated short-time power frequency withstand voltage(dry)    kvInterphase or to ground 42,fructure 48
Rated short-circuit breaking current                              kA20/2531.540
Rated current                                                             A630/1250

630/1250/

1600/2000/

2500/3150

1250/1600/

2000/2500/

3150/4000

Rated thermostability current(valid)kA20/2531.540
Rated dynamic stability current(peak)   kA 50/6380100
Rated short-circuit making current(peak)                              kA50/6380100
Power frequency withstand voltage of secondary circuit(1 min) v2000
Rated working current of overcurrent and tripping coil A5
Rated operating sequence                                             0-0.3s-CO-180s -CO/0-180s-CO-180s-CO(40KA)
Rated thermostability times4
Rated single/back to back capacitor bank breaking current                  A 630/400            800/400(40kA) 
Mechanical life                                           times10000
     
Note:It need to be forced coolingwhen rated current is 4000A          Rated characteristics can be given on requirment



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.