Main Technical  Data  
Rated voltage                                            kv7.2
Rated current                                            A250/400/630
Rated frequency                                         Hz50
Rated short-time power frequency withstand voltage(1min)     kv32
Rated lighting impulse withstand voltage                     kv65
Rated making current                         kA2.5/4.0/6.3
Rated breaking current,max                    kA2.0/3.2/5.0
Rated breaking current,min                    kA50/80/125
Rated  breaking current,limit kA2.5/4.0/6.3
Rated short-time withstand current                         kA2.5/4.0/6.3
Rated duration of short-circuit                              s4
Mechanical life                                           times30×10000
Electricity life AC-3times25×10000
Electricity life AC-4times10×10000
Rated contact strokemm6±1
Contact closing force due to bellows and atmosphere          N70±30
Counterforce at rated contact stroke                          N110±40
Circuit resistance at rated contact atmosphere force                      μΩ≤60
Shelf life                                                  years20
Contact erosion limit                                       mm3
Weight of moving parts                                                                             kg≤0.6
Mechanical Data Required For Matched Vacuum Switchgear                                             
Average opening speed                                   m/s0.6±0.2
Average closing speed                                    m/s0.3±0.1
Added contact force                                       N110±10
Contact bouncing duration at closing operation                ms≤2
Contact bouncing bank amplitude of opening operation         ms≤2
Three-pole simultaneity                                     ms≤1
   